Pool Boiler Temperature Controller: Difference between revisions
Matt Parnell (talk | contribs) |
Matt Parnell (talk | contribs) |
||
| (17 intermediate revisions by the same user not shown) | |||
| Line 14: | Line 14: | ||
* The controller functionality shall help improve boiler function and longevity without adding unnecessary complexity. | * The controller functionality shall help improve boiler function and longevity without adding unnecessary complexity. | ||
* The core function (temperature control) shall be performed by a proven, durable controller. In this case, a Euroterm | * The core function (temperature control) shall be performed by a proven, durable controller. In this case, a Euroterm 3508 was chosen due to its enhanced logic control capabilities. | ||
* The [[Pool_Systems_Automation|automation system]] shall not be required for operation. Failure of other components should have minimal impact upon its operation. | * The [[Pool_Systems_Automation|automation system]] shall not be required for operation. Failure of other components should have minimal impact upon its operation. | ||
| Line 23: | Line 23: | ||
=== LCD Display === | === LCD Display === | ||
An LCD display on the front of the controller indicates the measured temperature of the boiler manifold (top-most value). A graphical bar shows the value relative to the typical minimum and maximum operating | An LCD display on the front of the controller indicates the measured temperature of the boiler manifold (top-most value). A graphical bar shows the value relative to the typical minimum and maximum operating bounds. Temperature thresholds for a [[#Low Temperature Fault|Low Temperature Fault]], [[#Stage 2|Stage 2]] operation, and a [[#High Temperature Fault|High Temperature Fault]] are displayed on the subsequent lines. All temperatures are displayed in degrees Fahrenheit. | ||
The <tt>OP1</tt> and <tt>OP2</tt> indicators (beacons) indicate that [[#Stage 1|Stage 1]] and/or [[#Stage 2|Stage 2]] operation is active, respectively. An <tt>ALM</tt> indicator is associated with a fault condition; user intervention may be required to restore boiler operation. Blinking <tt>H</tt> and/or <tt>J</tt> indicators indicate communication port activity. | The <tt>OP1</tt> and <tt>OP2</tt> indicators (beacons) indicate that [[#Stage 1|Stage 1]] and/or [[#Stage 2|Stage 2]] operation is active, respectively. An <tt>ALM</tt> indicator is associated with a fault condition; user intervention may be required to restore boiler operation. Blinking <tt>H</tt> and/or <tt>J</tt> indicators indicate communication port activity. | ||
| Line 51: | Line 51: | ||
The boiler temperature is greater than the [[#Stage 2|Stage 2]] threshold, and [[#Stage 2| Stage 2]] is disabled as a result. This is not a fault condition, though it may indicate sub-optimal operation. Only [[#Stage 1|Stage 1]] heating is enabled. | The boiler temperature is greater than the [[#Stage 2|Stage 2]] threshold, and [[#Stage 2| Stage 2]] is disabled as a result. This is not a fault condition, though it may indicate sub-optimal operation. Only [[#Stage 1|Stage 1]] heating is enabled. | ||
The [[#Stage 2| Stage 2]] threshold is the temperature value to the right of the <tt>Stg2</tt> identifier on the display, and should typically be set to TBD. To adjust this threshold, see the [[#Threshold Adjustment|Threshold Adjustment]] section below. | The [[#Stage 2| Stage 2]] threshold is the temperature value to the right of the <tt>Stg2</tt> identifier on the display, and should typically be set to <span style="background:yellow">TBD</span>. To adjust this threshold, see the [[#Threshold Adjustment|Threshold Adjustment]] section below. | ||
If this state is active, [[Pool_Boiler#Recirculation_Valve|adjustment of the recirculation valve position]] should be considered. Since operating only in [[#Stage 1| Stage 1]] produces less heat, the ability to heat the pool is reduced. This is primarily an issue where the amount of heat loss in the pool exceeds the capability of [[#Stage 1| Stage 1]] heating (i.e. the pool cools faster than it can be heated). | If this state is active, [[Pool_Boiler#Recirculation_Valve|adjustment of the recirculation valve position]] should be considered. Since operating only in [[#Stage 1| Stage 1]] produces less heat, the ability to heat the pool is reduced. This is primarily an issue where the amount of heat loss in the pool exceeds the capability of [[#Stage 1| Stage 1]] heating (i.e. the pool cools faster than it can be heated). | ||
| Line 61: | Line 61: | ||
==== Low Temperature Fault ==== | ==== Low Temperature Fault ==== | ||
The boiler temperature is less than the low | The boiler temperature is less than the low temperature threshold and both stages are disabled as a result. The low-temperature threshold should typically be set to <span style="background:yellow">TBD</span>. This is a latching fault and must be cleared via the front panel before the boiler will operate. | ||
Before attempting to clear the fault, the source of the fault should be cleared. See the [[Pool_Boiler#Low_Temperature_Fault|Pool Boiler Low Temperature Fault]] section for further information ([[Pool_Boiler#Recirculation_Valve|recirculation valve adjustment]] may be needed). | |||
==== High Temperature Fault ==== | ==== High Temperature Fault ==== | ||
The boiler temperature is greater than the high-temperature threshold and both stages are disabled as a result. | The boiler temperature is greater than the high-temperature threshold and both stages are disabled as a result. The high temperature threshold should typically be set to <span style="background:yellow">TBD</span>. This is a latching fault and must be cleared via the front panel before the boiler will operate. | ||
=== Threshold Adjustment === | |||
Threshold adjustment is typically not necessary or recommended. Instead, it is recommended that the system be evaluated for deficiencies. | |||
If a parameter must be adjusted, press the scroll button (left of the down arrow) to move the up/down cursor to the desired parameter. Press the up/down keys to adjust the temperature. Internal bounds limit how high or low a parameter may be adjusted. Use extreme caution in adjusting each parameter, as each could have significant impacts upon boiler operation. | |||
=== Other Buttons === | === Other Buttons === | ||
| Line 85: | Line 87: | ||
=== Low Operator === | === Low Operator === | ||
The low operator is activated when the following conditions are true: | The low operator is activated (the relay contact is closed) when the following conditions are true: | ||
* The RTD is producing valid feedback (not shorted or open-circuit). | * The RTD is producing valid feedback (not shorted or open-circuit). | ||
* The boiler temperature is below the | * The boiler temperature is below the high temperature fault threshold (timing rules apply). | ||
The low operator may be released when any of the prior conditions are no longer met. In addition, it may be released when: | The low operator may be released when any of the prior conditions are no longer met. In addition, it may be released when: | ||
| Line 103: | Line 104: | ||
=== High Operator === | === High Operator === | ||
The high operator is activated when the following conditions are true: | The high operator is activated (the relay contact is closed) when the following conditions are true: | ||
* All conditions for the low operator are met | * All conditions for the [[#Low Operator|low operator]] are met. | ||
* The boiler temperature is below the second stage threshold (timing rules apply). | * The boiler temperature is below the second stage threshold (timing rules apply). | ||
== Controller Hardware == | == Controller Hardware == | ||
=== As Shipped Configuration === | === As-Shipped Configuration === | ||
When shipped from the factory, a long configuration code is printed on the side of the controller to identify the configuration. The code on the installed controller is decoded below: | |||
{| class="wikitable" | {| class="wikitable" | ||
| Line 166: | Line 168: | ||
|LO | |LO | ||
|Isolated Single Logic Output | |Isolated Single Logic Output | ||
| | |May not be used. | ||
|- | |- | ||
!IO Slot 2 | !IO Slot 2 | ||
|D4 | |D4 | ||
|DC Control | |DC Control | ||
|Will not be used. | |Will not be used; see modifications below. | ||
|- | |- | ||
!IO Slot 3 | !IO Slot 3 | ||
|TK | |TK | ||
|Triple Contact Input | |Triple Contact Input | ||
| | |May not be used. | ||
|- | |- | ||
!H Comms Slot | !H Comms Slot | ||
|PD | |PD | ||
|Profibus with D-type Connector | |Profibus with D-type Connector | ||
|Module is an AH026222U002. | |Module is an AH026222U002 (visually identified). | ||
|- | |- | ||
!J Comms Slot | !J Comms Slot | ||