=== Low Operator ===
=== Low Operator ===


The low operator is activated when the following conditions are true:
The low operator is activated (the relay contact is closed) when the following conditions are true:


* The RTD is producing valid feedback (not shorted or open-circuit).
* The RTD is producing valid feedback (not shorted or open-circuit).
* The boiler temperature is below the over-temperature shutdown threshold (timing rules apply).
* The boiler temperature is below the high temperature fault threshold (timing rules apply).


The low operator may be released when any of the prior conditions are no longer met.  In addition, it may be released when:
The low operator may be released when any of the prior conditions are no longer met.  In addition, it may be released when:
Line 104: Line 104:
=== High Operator ===
=== High Operator ===


The high operator is activated when the following conditions are true:
The high operator is activated (the relay contact is closed) when the following conditions are true:


* All conditions for the low operator are met.
* All conditions for the [[#Low Operator|low operator]] are met.
* The main valve (MV) is active.
* The boiler temperature is below the second stage threshold (timing rules apply).
* The boiler temperature is below the second stage threshold (timing rules apply).