=== Low Operator ===
=== Low Operator ===


The low operator is activated when the following conditions are true:
The low operator is activated (the relay contact is closed) when the following conditions are true:


* The RTD is producing valid feedback (not shorted or open-circuit).
* The RTD is producing valid feedback (not shorted or open-circuit).
Line 104: Line 104:
=== High Operator ===
=== High Operator ===


The high operator is activated when the following conditions are true:
The high operator is activated (the relay contact is closed) when the following conditions are true:


* All conditions for the low operator are met.
* All conditions for the [[#Low Operator|low operator]] are met.
* The main valve (MV) is active.
* The boiler temperature is below the second stage threshold (timing rules apply).
* The boiler temperature is below the second stage threshold (timing rules apply).