== Theory of Operation ==
== Theory of Operation ==
=== Operation Sequence ===


The operation sequence below is based upon the procedure described in the LCD Series manual, with adaptations per the installation wiring.
The operation sequence below is based upon the procedure described in the LCD Series manual, with adaptations per the installation wiring.


==== Stage 0: Water Level OK ====
=== Stage 0: Water Level OK ===


The low-water cut-out disconnects power from the 75 VA control transformer in the boiler.  This prevents boiler operation when a low water situation is encountered.
The low-water cut-out disconnects power from the 75 VA control transformer in the boiler.  This prevents boiler operation when a low water situation is encountered.


==== Stage A: Demand for Heat ====
=== Stage A: Demand for Heat ===


A demand for heat occurs when all of the following conditions are met:
A demand for heat occurs when all of the following conditions are met:
Line 82: Line 84:
# The automation system relay CR2110 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X10]].
# The automation system relay CR2110 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X10]].


==== Stage B: Temperature and Water Flow OK ====
=== Stage B: Temperature and Water Flow OK ===


The temperature and water flow are deemed OK when:
The temperature and water flow are deemed OK when:
Line 100: Line 102:
# The automation system relay CR2111 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X11]].
# The automation system relay CR2111 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X11]].


==== Stage C: Low Air Pressure OK ====
=== Stage C: Low Air Pressure OK ===


The low air pressure switch closes in response to sufficient positive pressure in the combustion chamber.
The low air pressure switch closes in response to sufficient positive pressure in the combustion chamber.
Line 117: Line 119:
NOTE: Flame fail/lockout is not considered here.  The present flame sense module (FSM), or "intermittent pilot ignition" module, does not include alarm contacts (UTEC 1003-638A).  The specified module, a UTEC 1003-61A is unavailable on the market at this time.  The alarm contacts are required to engage R1, the flame fail/lockout relay.  This is problematic, as it would allow the ignition transformer to spark indefinitely, eventually resulting in component failure.  As a work-around, the automation system provides a monitored lockout function via the <b>Boiler Disable</b> relay.
NOTE: Flame fail/lockout is not considered here.  The present flame sense module (FSM), or "intermittent pilot ignition" module, does not include alarm contacts (UTEC 1003-638A).  The specified module, a UTEC 1003-61A is unavailable on the market at this time.  The alarm contacts are required to engage R1, the flame fail/lockout relay.  This is problematic, as it would allow the ignition transformer to spark indefinitely, eventually resulting in component failure.  As a work-around, the automation system provides a monitored lockout function via the <b>Boiler Disable</b> relay.


==== Stage D ====
=== Stage D: Main Gas Valve On ===
 
The main gas valve (also referred to as the "main valve" or MV) turns on (becomes active) when the flame sense module (FSM) confirms the presence of the pilot flame.


Description pending.
Once this has occurred:
 
# Relay R8 is energized to disable the spark generator transformer.
# The MAIN GAS indicator on the boiler is illuminated.
# The automation system relay CR2113 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X13]].
# The relay in the [[Pool Temperature Controller|pool temperature controller]] is energized, which provides confirmation that a request for heat has been satisfied.
# The boiler temperature controller [[Pool Boiler Temperature Controller#Main Valve Active|main valve active]] input (relay) is energized.


==== Stage E ====
=== Stage E: Stage 2 Active ===


Description pending.
Description pending.


=== Control Interlocks ===
== Summary of Control Interlocks ==


The list below includes interlocks with electrical interfaces only and is intended to align with the CSD-1.  This table is for reference only; the CSD-1 should always be considered the master.
The list below includes interlocks with electrical interfaces only and is intended to align with the CSD-1.  This table is for reference only; the CSD-1 should always be considered the master.