The hot and neutral connections within junction boxes and in the breaker panel are marked with the same identifying letters as shown in this drawing. | The hot and neutral connections within junction boxes and in the breaker panel are marked with the same identifying letters as shown in this drawing. | ||
The receptacles on the pool deck (circuits A and D) share a 20 A circuit. The receptacle near the tennis courts has a dedicated 20 A feed. Due to the long run and use of #12 AWG wire, some voltage drop should be expected on this outlet is heavy loads are used. Observe that GFCI protection is provided via the in-line units inside the pump house; receptacles themselves to not contain GFCI protection but are GFCI protected. | |||