Pool Systems Dashboard: Difference between revisions

From Fairway Farms Swim Club
Jump to navigation Jump to search
Line 12: Line 12:


{| class="wikitable"
{| class="wikitable"
!Range
!Range<br>(psi)
!Color
!Color
!Description
!Description
|-
|-
|0 to 4 psi
|0-4
|Red
|Red
|Critically Low Pressure (Pump/Flow Issue)
|Critically Low Pressure (Pump/Flow Issue)
|-
|-
|4 to 8 psi
|4-8
|Yellow
|Yellow
|Low Pressure (Flow Issue)
|Low Pressure (Flow Issue)
|-
|-
|8 to 18 psi
|8-18
|Green
|Green
|Normal Operating Pressure
|Normal Operating Pressure
|-
|-
|18+ psi
|18+
|Yellow/Red
|Yellow/Red
|Backwash Recommended
|Backwash Recommended

Revision as of 18:48, 2 September 2021

Information about the visual dashboard (associated with the automation system) will follow shortly.

Gauges

Tank Pressure

An example of a tank pressure gauge.

Shows the pressure in pounds per square inch (psi) for a sand filter tank.

The color bands are determined as follows:

Range
(psi)
Color Description
0-4 Red Critically Low Pressure (Pump/Flow Issue)
4-8 Yellow Low Pressure (Flow Issue)
8-18 Green Normal Operating Pressure
18+ Yellow/Red Backwash Recommended

For consistent indication, the values above and dashboard visualization thresholds should always align with those defined within the PLC code.

Tank pressure is lowest when the strainer basket is clean and the sand filters have been recently backwashed. If pump outflow is restricted enough (in an effort to maintain proper flow, it is possible for pressure to dip into the "Low Pressure" range. This is not necessarily a cause for any concern.