Pool Boiler Temperature Controller: Difference between revisions
→Operating States
Matt Parnell (talk | contribs) |
Matt Parnell (talk | contribs) |
||
| Line 61: | Line 61: | ||
==== Low Temperature Fault ==== | ==== Low Temperature Fault ==== | ||
The boiler temperature is less than the low temperature threshold and both stages are disabled as a result. The low-temperature threshold should typically be set to <span style="background:yellow">TBD</span>. | The boiler temperature is less than the low temperature threshold and both stages are disabled as a result. The low-temperature threshold should typically be set to <span style="background:yellow">TBD</span>. This is a latching fault and must be cleared via the front panel before the boiler will operate. | ||
Before attempting to clear the fault, the source of the fault should be cleared. See the [[Pool_Boiler#Low_Temperature_Fault|Pool Boiler Low Temperature Fault]] section for further information ([[Pool_Boiler#Recirculation_Valve|recirculation valve adjustment]] may be needed). | |||
==== High Temperature Fault ==== | ==== High Temperature Fault ==== | ||
The boiler temperature is greater than the high-temperature threshold and both stages are disabled as a result. The high temperature threshold should typically be set to <span style="background:yellow">TBD</span>. | The boiler temperature is greater than the high-temperature threshold and both stages are disabled as a result. The high temperature threshold should typically be set to <span style="background:yellow">TBD</span>. This is a latching fault and must be cleared via the front panel before the boiler will operate. | ||
This is a latching fault and must be cleared via the front panel before the boiler will operate. | |||
=== Threshold Adjustment === | === Threshold Adjustment === | ||