Pool Systems Automation: Difference between revisions

Line 32: Line 32:
* 1 x Temperature Transmitter (TT) prior to the inlet of the boiler.  This unit is used as the feedback for the [[Pool Heater Temperature Controller|temperature controller]], which raises a call for heat to the boiler.
* 1 x Temperature Transmitter (TT) prior to the inlet of the boiler.  This unit is used as the feedback for the [[Pool Heater Temperature Controller|temperature controller]], which raises a call for heat to the boiler.
* 1 x Flow Transmitter (FT), pH probe and ORP probe.  These sensors are fed into the Chemtrol PC2100.
* 1 x Flow Transmitter (FT), pH probe and ORP probe.  These sensors are fed into the Chemtrol PC2100.
The following sensors are used:
{| class="wikitable"
!Parameter
!Sensor Part
!Range
!Output
|-
|Pressure
|Measurement Specialties MSP-300-100-P-4-N-1
|0-100 psi
|1-5 V analog
|-
|Flow
|GF Signet MK515.3P1
|0.3 to 6 m/s<br>1 to 20 ft/s
|Sine Wave (analog)
|-
|Depth
|ALS-MPM-2F
|0-5 meters
|4-20 mA
|-
|Temperature
|TBD - PT100 RTD
| -40 to +400 degC
|Resistive
|}


== Drawings ==
== Drawings ==