Pool Systems Automation: Difference between revisions

Line 28: Line 28:
==== Filter Tank Pressure ====
==== Filter Tank Pressure ====


Four filter tank pressures are monitored by sensors with internal signal conditioning.  When fed by a 24 VDC (each sensor is independently fused), a 1 V to 5 V output corresponds with 0 to 100 PSI of pressure.
Four filter tank pressures are monitored by sensors with internal signal conditioning.  When fed by a 24 VDC (each sensor is independently fused), a 1 V to 5 V output corresponds with 0 to 100 psi of pressure.


A value is considered valid if the measured voltage is 1 V or greater (less than 1 V suggests an open circuit or failed sensor).  The low and high thresholds are somewhat arbitrary, and based upon observation.  A nominal pressure of 10 PSI is assumed (add 8 PSI to the limit per PHTA guidelines for a single-gauge backwash threshold).
A value is considered valid if the measured voltage is 1 V or greater (less than 1 V suggests an open circuit or failed sensor).  The low and high thresholds are somewhat arbitrary, and based upon observation.  A nominal pressure of 10 psi is assumed (add 8 psi to the limit per PHTA guidelines for a single-gauge backwash threshold).


{| class="wikitable"
{| class="wikitable"
Line 40: Line 40:
|-
|-
|Pump Operating
|Pump Operating
|< 8 PSI
|< 8 psi
|Pressure Low
|Pressure Low
|<tt>Flt Tank Pres L</tt>
|<tt>Flt Tank Pres L</tt>
Line 46: Line 46:
|-
|-
|Pump Operating
|Pump Operating
|&GreaterEqual; 8 PSI and < 18 PSI
|&GreaterEqual; 8 psi and < 18 psi
|Pressure OK
|Pressure OK
|None
|None
Line 52: Line 52:
|-
|-
|Pump Operating
|Pump Operating
|&GreaterEqual; 18 PSI
|&GreaterEqual; 18 psi
|Pressure High
|Pressure High
|<tt>Flt Tank Pres H</tt>
|<tt>Flt Tank Pres H</tt>
Line 58: Line 58:
|}
|}


When in the <b>Pump Startup</b>, <b>Pump Operating</b> or <b>Backwash</b> state, each tank pressure is briefly shown on the LCD in PSI.  If the value is not valid, <tt>Fault</tt> is shown in place of a pressure value.
When in the <b>Pump Startup</b>, <b>Pump Operating</b> or <b>Backwash</b> state, each tank pressure is briefly shown on the LCD in psi.  If the value is not valid, <tt>Fault</tt> is shown in place of a pressure value.


==== Water Flow ====