Pool Systems Dashboard
Information about the visual dashboard (associated with the automation system) will follow shortly.
Gauges
Gauge measurements are averaged in both the PLC and dashboard software. Gauges may take several seconds (or longer) to respond to significant changes in system conditions.
Tank Pressure

Shows the pressure in pounds per square inch (psi) for a sand filter tank.
The color bands are determined as follows:
| Range (psi) |
Color | Description |
|---|---|---|
| 0-4 | Red | Critically Low Pressure (Pump/Flow Issue) |
| 4-8 | Yellow | Low Pressure (Flow Issue) - Consider Cleaning the Strainer Basket |
| 8-18 | Green | Normal Operating Pressure |
| 18+ | Yellow/Red | Backwash Recommended |
For consistent indication, the values above and dashboard visualization thresholds should always align with those defined within the PLC thresholds.
Tank pressure is lowest when the strainer basket is clean and the sand filters have been recently backwashed. If pump outflow is restricted enough (in an effort to maintain proper flow, it is possible for pressure to dip into the "Low Pressure" range. This is not necessarily a cause for any concern.
If the associated sensor is in a fault state (the sensor has failed, there is a wiring/fuse fault or the connector is unplugged), the gauge will show a value of 0.0. A fault state is indicated by the PLC and the stack light. If the gauge is not visible (the block is blank), a communication error with the PLC has occurred or a software issue is present on the dashboard PC. Consult the system administrator.
Surge Tank Depth

Shows the depth in inches for the surge tank.
The color bands are determined as follows:
| Range (psi) |
Color | Description |
|---|---|---|
| TBD | TBD | TBD |
Out Flow

Shows the out flow rate in gallons per minute (GPM).
Inlet Temperature

Shows the inlet temperature in degrees Fahrenheit (°F).
The color bands are determined as follows:
| Range (psi) |
Color | Description |
|---|---|---|
| ≤ 79 | Blue | Low Temperature (Temperature Controller Alarm) |
| 79-81 | Yellow | Low Temperature (Outside of Controlled Bounds) |
| 81+ | Green | Normal Temperature |
The boiler is nominally set to 82 °F. Controller hysteresis keeps the temperature to within ±1 °F or less. The temperature controller enters an "alarm" state indicating that the boiler may be in a fault state once the temperature is below 79 °F. During hot summer days, temperatures of 82 °F to 87 °F are expected and normal.
pH

Shows the sampled water pH.
ORP

Shows the sampled water oxidation reduction potential (ORP).