Pool Systems Dashboard
Information about the visual dashboard (associated with the automation system) will follow shortly.
System
Hardware
Communication with the PLC and temperature controller requires a functional WiFi device network.
Software
Gauges
Gauge measurements are averaged in both the PLC and dashboard software. Gauges may take several seconds (or longer) to respond to significant changes in system conditions.
Tank Pressure

Shows the pressure in pounds per square inch (psi) for a sand filter tank per a PLC measurement (via WiFi link).
The color bands are determined as follows:
| Range (psi) |
Color | Description |
|---|---|---|
| 0-4 | Red | Critically Low Pressure (Pump/Flow Issue) |
| 4-8 | Yellow | Low Pressure (Flow Issue) - Consider Cleaning the Strainer Basket |
| 8-18 | Green | Normal Operating Pressure |
| 18+ | Yellow/Red | Backwash Recommended |
For consistent indication, the values above and dashboard visualization thresholds should always align with those defined within the PLC thresholds.
Tank pressure is lowest when the strainer basket is clean and the sand filters have been recently backwashed. If pump outflow is restricted enough (in an effort to maintain proper flow, it is possible for pressure to dip into the "Low Pressure" range. This is not necessarily a cause for any concern.
If the associated sensor is in a fault state (the sensor has failed, there is a wiring/fuse fault or the connector is unplugged), the gauge will show a value of 0.0. A fault state is indicated by the PLC and the stack light. If the gauge is not visible (the block is blank), a communication error with the PLC has occurred or a software issue is present on the dashboard PC. Consult the system administrator.
Surge Tank Depth

Shows the depth in inches for the surge tank.
The color bands are determined as follows:
| Range (in) |
Color | Description |
|---|---|---|
| < 16 | Red | Critical Depth |
| 16-46 | Yellow | Low Depth (Auto-Fill Threshold) |
| 46-60 | Green | Nominal Depth (See Note) |
| 60-76 | Blue | Excess Depth |
| > 76 | Red | Overflow Depth |
Note: The "nominal" depth of the surge tank is subject to future revision. At this time, lacking a proper drain modulating valve, it is not possible to provide "surge" capacity (keep the tank depth lowered during periods of high gutter flow). As a result, some portion of the "nominal" and "excess" depth is expected when the pool level is high and/or there is a large amount of activity in the pool. Ideally, the surge tank should usually remain below the gutter inlet level.
When the critical depth is met, this may result in pump shutdown (per the PLC) to prevent taking on air. The surge tank water level is insufficient to maintain operation. When enabled, auto-fill begins at the upper end of the "low" depth threshold and ends when the upper end of the "nominal" depth is met. A large amount of surge tank depth hysteresis is needed when an actual pool depth measurement is lacking.
The tank nears overflow at the "overflow" depth threshold. No specific action is taken by the PLC at this point.
Out Flow

Shows the out flow rate in gallons per minute (GPM).
The color bands are determined as follows:
| Range (°F) |
Color | Description |
|---|---|---|
| < 490 | Red | Very Low Flow |
| 490-570 | Yellow | Low Flow (See Note) |
| 570-670 | Green | Optimal Flow |
| > 670 | Yellow | High Flow |
A target flow rate of 600 GPM has been established for manual adjustment. This flow rate:
- Meets the minimum pool turnover rate of 4 times per day (every 6 hours) for a 203,500 gallon pool.
- Is within some margin of the maximum flow rate set by the sand filters (140 GPM x 4 = 580 GPM).
To prevent channeling in the sand filters, an upper bound of 670 GPM has been set (somewhat arbitrarily). The operator should try to keep as close to 600 GPM operation as possible (without dipping below 570 GPM).
Inlet Temperature

Shows the inlet temperature in degrees Fahrenheit (°F) per the temperature controller measurement (via WiFi link). This temperature is measured directly after the filter tanks, prior to the boiler loop (refer to the Process Flow Diagram).
The color bands are determined as follows:
| Range (°F) |
Color | Description |
|---|---|---|
| < 79 | Blue | Low Temperature (Temperature Controller Alarm) |
| 79-81 | Yellow | Low Temperature (Outside of Controlled Bounds) |
| 81+ | Green | Normal Temperature |
The boiler is nominally set to 82 °F. Controller hysteresis keeps the temperature to within ±1 °F or less. The temperature controller enters an "alarm" state indicating that the boiler may be in a fault state once the temperature is below 79 °F. During hot summer days, temperatures of 82 °F to 87 °F are expected and normal.
pH

Shows the sampled water pH per a Chemtrol Pool Controller measurement (via RS-485/Ethernet link).
The color bands are determined as follows:
| Range (°F) |
Color | Description |
|---|---|---|
| < 7.2 | Red | Corrosive Water (See Note) |
| 7.2-7.4 | Yellow | pH Low |
| 7.4-7.6 | Green | pH Ideal |
| 7.6-7.8 | Yellow | pH High |
| > 7.8 | Red | Scaling Water (See Note) |
Note: Ideal pH is between 7.4 and 7.6. A pH between 7.2 and 7.8 is generally acceptable (though possibly too low or too high). A pH below 7.2 or above 7.8 may be problematic; verify by calculating the Langelier Saturation Index (LSI).
ORP

Shows the sampled water oxidation reduction potential (ORP) per a Chemtrol Pool Controller measurement (via RS-485/Ethernet link).
Graphs
ORP