==== Filter Tank Pressure ====
==== Filter Tank Pressure ====
[[File:Pool Filter Tank Pressure Gauges.jpg|thumbnail|A set of pressure gauges.  Per the design principle, all electronic measurements have an accompanying manual gauge.]]


Four [[Pool Filter Tanks|filter tank]] pressures are monitored by [[Pool Systems Automation#Sensors|sensors]] with internal signal conditioning.  When fed by a 24 VDC (each sensor is independently fused), a 1 V to 5 V output corresponds with 0 to 100 psi of pressure.
Four [[Pool Filter Tanks|filter tank]] pressures are monitored by [[Pool Systems Automation#Sensors|sensors]] with internal signal conditioning.  When fed by a 24 VDC (each sensor is independently fused), a 1 V to 5 V output corresponds with 0 to 100 psi of pressure.


A value is considered valid if the measured voltage is 1 V or greater (less than 1 V suggests an open circuit or failed sensor).  The low and high thresholds are somewhat arbitrary, and based upon observation.  A nominal pressure of 10 psi is assumed (add 8 psi to the limit per PHTA guidelines for a single-gauge backwash threshold).
A value is considered valid if the measured voltage is 1 V or greater (less than 1 V suggests an open circuit or failed sensor).  The low and high thresholds are somewhat arbitrary and based upon observation.  A nominal pressure of 10 psi is assumed (add 8 psi to the limit per PHTA guidelines for a single-gauge backwash threshold).