Pool Main Pump Motor: Difference between revisions
Jump to navigation
Jump to search
→Variable Frequency Drive (VFD)
Matt Parnell (talk | contribs) |
Matt Parnell (talk | contribs) |
||
| Line 114: | Line 114: | ||
== Variable Frequency Drive (VFD) == | == Variable Frequency Drive (VFD) == | ||
IMPORTANT: At this time, this section is for investigation purposes only. It has not been determined when/if a VFD will be implemented. | <b>IMPORTANT:</b> At this time, this section is for investigation purposes only. It has not been determined when/if a VFD will be implemented. | ||
An Automatic Direct DURApulse GS23-2015 VFD has been chosen over multiple competing options. The feature set and pricing is very competitive. | |||
=== Requirements === | === Requirements === | ||
* | * Must withstand an ambient operating range in the 40 °C to 50 °C (122 °F) range. For the GS23-2015 at 75% load, 50 °C, no de-rating is necessary up to a 4 kHz carrier frequency (SVPWM mode). | ||
* | * Must be compatible with 240 VAC high-leg delta. | ||
=== Safety === | === Safety === | ||
A safety relay (reset and E-stop circuits) and additional contactor (maybe two contactors w/o STO) are likely required. | A safety relay (reset and E-stop circuits) and additional contactor (maybe two contactors w/o STO) are likely required. | ||
A load reactor likely will not be used, nor does it necessarily eliminate the need for shielded VFD cabling. | A load reactor likely will not be used, nor does it necessarily eliminate the need for shielded VFD cabling. | ||
=== Bill of Materials === | === Bill of Materials === | ||
| Line 245: | Line 201: | ||
<b>Not Included:</b> DIN rail, terminals, small fuse terminal(s), control wire, etc. | <b>Not Included:</b> DIN rail, terminals, small fuse terminal(s), control wire, etc. | ||
=== Motor Cable === | |||
Shielded VFD cabling may be required to contain high-frequency emissions. Automation Direct has #8 AWG 4-conductor XLPE insulated shielded cable, rated for 50 A at 75 °C (NEC 310.15 (B), assumes 30 °C ambient) for $8.08/ft (August 2021 pricing). The cable is made in USA by Southwire. This cable has an OD of 0.87 inches and minimum bend radius of 10 inches. Calculations suggest a 1-1/4" conduit may be necessary to pull a cable of this diameter with adequate fill margin. The existing PVC conduit appears to be about 3/4" (to confirm), which would need to be replaced. | |||
=== Configuration === | |||
* Use Variable Torque (VT) mode for pump control (power is proportional to the cube of the speed) | |||