Pool Boiler Temperature Controller: Difference between revisions

Jump to navigation Jump to search
No edit summary
Line 31: Line 31:
* The RTD is producing valid feedback (not shorted or open-circuit).
* The RTD is producing valid feedback (not shorted or open-circuit).
* The boiler temperature is below the over-temperature shutdown threshold (timing rules apply).
* The boiler temperature is below the over-temperature shutdown threshold (timing rules apply).
* The boiler temperature is above the minimum temperature threshold (timing rules apply).
 
The low operator may be released when any of the prior conditions are no longer met.  In addition, it may be released when:
 
* The first stage is active and the boiler temperature is below the minimum temperature threshold.  This condition is applied after a warm-up period has elapsed.


The low operator activates the first stage burner once the boiler interlock conditions and timing are satisfied.
The low operator activates the first stage burner once the boiler interlock conditions and timing are satisfied.