Pool Main Pump Motor: Difference between revisions
Jump to navigation
Jump to search
→Run
Matt Parnell (talk | contribs) |
Matt Parnell (talk | contribs) (→Run) |
||
| Line 44: | Line 44: | ||
Pressing the <b>Run</b> pushbutton causes the VFD digital input (FWD/DI1) to go HIGH (+24V). Assuming the safety module is reset, the VFD will operate (ramp up?) to full speed (60 Hz). The speed may be reduced via closed-loop control from the automation system (based upon flow meter feedback). By defaulting to 60 Hz, the motor can be operated normally without the automation system, using the butterfly valve on the output side of the pump to adjust flow. | Pressing the <b>Run</b> pushbutton causes the VFD digital input (FWD/DI1) to go HIGH (+24V). Assuming the safety module is reset, the VFD will operate (ramp up?) to full speed (60 Hz). The speed may be reduced via closed-loop control from the automation system (based upon flow meter feedback). By defaulting to 60 Hz, the motor can be operated normally without the automation system, using the butterfly valve on the output side of the pump to adjust flow. | ||
A VFD digital output (DO1) illuminates the green LED embedded in the <b>Run</b> pushbutton to provide status feedback. | |||
==== Programmed Stop ==== | ==== Programmed Stop ==== | ||