=== Line Reactor === | |||
Automation Direct recommends an LR-2015 (46.2 A, 0.22 mH, 3-phase, 4.25" H x 7.2" W x 4.75" D) for $179 on Automation Direct. | |||
A 3% impedance reactor absorbs transients and prevents nuisance tripping of drives in most applications. A 3% impedance line reactor is typical for the line side. A 5% impedance reactor can be used if the harmonic content is severe or if IEEE519 recommendations should be met. The reactor impedance magnitude is said to be equal to the voltage drop. | |||
Multiple alternatives to the LR-2015 have been evaluated: | |||
* MTE RL-04501 (45 A, 0.300 mH, 3-phase, 4.60" H x 8.91" W x 7.13" D) for $289.31 on Galco or far less on eBay. This is a very large part. | |||
* MTE RLW-004601 (42 A, 3.68" H x 6.00" W x 5.76" D). Not readily available. | |||
* TCI KDRD24L (208/240 VAC 48 A 15 HP, 3-phase, 3% - Low Z, 3.82" H x 6.95" W x 5.57" D). $195.94 on Galco (eBay TBD). | |||
* Hammond CRX0046AC (46 A, 0.21 mH, 15 HP, 3-phase, 3%, 5.00" L x 6.13" H x 4.38" D, 40 Watts). Not readily available on eBay. | |||
=== Drawings === | |||
[[File:FFSC-005 Pg 7 - VFD Panel Reactor Placement Study.png|300px]] | |||
[[File:FFSC-005 Pg 10 - Main Pump Motor VFD.png|300px]] | |||
=== Bill of Materials === | === Bill of Materials === | ||
| Line 71: | Line 90: | ||
The list below is updated as of 1-Jan-2022. Some items have been pre-emptively purchased (anticipating board approval; can be re-sold otherwise). | The list below is updated as of 1-Jan-2022. Some items have been pre-emptively purchased (anticipating board approval; can be re-sold otherwise). | ||
The list below does not include parts for "Programmed Stop", nor does it include cooling fans and filters. | The list below does not include parts for "Programmed Stop", nor does it include cooling fans and filters. The VFD motor cable (if used) is also not included. | ||
{| class="wikitable" | {| class="wikitable" | ||
| Line 159: | Line 178: | ||
<b>Not Included:</b> DIN rail, terminals, small fuse terminal(s), control wire, etc. | <b>Not Included:</b> DIN rail, terminals, small fuse terminal(s), control wire, etc. | ||
=== Motor Cable === | === Motor Cable === | ||