Pool Main Pump Motor: Difference between revisions

Jump to navigation Jump to search
Line 278: Line 278:
=== Motor Cable ===
=== Motor Cable ===


Shielded VFD cabling may be required to contain high-frequency emissions.  Automation Direct has #8 AWG 4-conductor XLPE insulated shielded cable, rated for 50 A at 75 °C (NEC 310.15 (B), assumes 30 °C ambient) for $8.08/ft (August 2021 pricing).  The cable is made in USA by Southwire.  This cable has an OD of 0.87 inches and minimum bend radius of 10 inches.  Calculations suggest a 1-1/4" conduit may be necessary to pull a cable of this diameter with adequate fill margin.  The existing PVC conduit appears to be about 3/4" (to confirm), which would need to be replaced.
Shielded VFD cabling may be required to contain high-frequency emissions.   
 
* Automation Direct has #8 AWG 4-conductor XLPE insulated shielded cable, rated for 50 A at 75 °C (NEC 310.15 (B), assumes 30 °C ambient) for $8.08/ft (August 2021 pricing).  The cable is made in USA by Southwire.  This cable has an OD of 0.87 inches and minimum bend radius of 10 inches.  Calculations suggest a 1-1/4" conduit may be necessary to pull a cable of this diameter with adequate fill margin.  The existing PVC conduit appears to be about 3/4" (to confirm), which would need to be replaced.
 
* In January 2022, there appears to be a low-cost option to purchase Lapp Kabel #760604 (4 x #6 AWG) VFD cable for less than $6/ft.  This cable has an OD of 25.5 mm (1.00 inches).


=== Bypass ===
=== Bypass ===

Navigation menu