Pool Main Pump Motor: Difference between revisions
Jump to navigation
Jump to search
→Line Reactor
Matt Parnell (talk | contribs) |
Matt Parnell (talk | contribs) |
||
| Line 159: | Line 159: | ||
A 3% impedance reactor absorbs transients and prevents nuisance tripping of drives in most applications and is typical for the line side. A 5% impedance reactor can be used if the harmonic content is severe or if IEEE519 recommendations should be met. The reactor impedance magnitude is said to be equal to the voltage drop. | A 3% impedance reactor absorbs transients and prevents nuisance tripping of drives in most applications and is typical for the line side. A 5% impedance reactor can be used if the harmonic content is severe or if IEEE519 recommendations should be met. The reactor impedance magnitude is said to be equal to the voltage drop. | ||
For 37 FLA (motor rating). Assume the VFD has about 97% efficiency (given loss is 391 W @ | |||
{| class="wikitable" | {| class="wikitable" | ||
| Line 175: | Line 177: | ||
|208/240 V | |208/240 V | ||
|46.2 A | |46.2 A | ||
|0.22 mH | |0.22 mH<br>(rated) | ||
|$179 | |$179 | ||
|Recommended for the LR-2015. | |Recommended for the LR-2015. | ||
| Line 184: | Line 186: | ||
| | | | ||
|45 A | |45 A | ||
|0.300 mH | |0.300 mH<br>(rated) | ||
|$289.31 (Galco) | |$289.31 (Galco) | ||
|Very large physical dimensions. | |||
|- | |- | ||
|TCI | |TCI | ||
| Line 192: | Line 195: | ||
| | | | ||
|40 A | |40 A | ||
| | |||
|- | |||
|TCI | |||
|KDRULD42L | |||
| | |||
|600 V | |||
|32 A | |||
|0.861 mH<br>(calculated) | |||
| | |||
|3% @ 575/600V | |||
|- | |||
|TCI | |||
|KLR35BTB | |||
| | |||
|480 V | |||
|35 A | |||
|0.315 mH<br>(calculated) | |||
| | |||
|1.5% @ 480V (0.315 mH), 3% @ 240V | |||
|- | |||
|TCI | |||
|KLR45BTB | |||
| | |||
|480 V | |||
|45 A | |||
|0.490 mH<br>(calculated) | |||
| | |||
|3% @ 480V | |||
|- | |||
|TCI | |||
|KDRULD2L | |||
| | | | ||
|} | |} | ||
* MTE RLW-004601 (42 A, 3.68" H x 6.00" W x 5.76" D). Not readily available. | * MTE RLW-004601 (42 A, 3.68" H x 6.00" W x 5.76" D). Not readily available. | ||
* TCI KDRD24L (208/240 VAC 48 A 15 HP, 3-phase, 3% - Low Z, 3.82" H x 6.95" W x 5.57" D). $195.94 on Galco (eBay TBD). | * TCI KDRD24L (208/240 VAC 48 A 15 HP, 3-phase, 3% - Low Z, 3.82" H x 6.95" W x 5.57" D). $195.94 on Galco (eBay TBD). | ||