This section has been updated to alter its context from research to implementation. A majority of the data for "other" VFD units has been removed. | |||
Yaskawa GA50U2042ABA: | |||
* The 2042 model sized for "normal duty" (ND) 15 HP which is appropriate for variable torque (VT) applications (i.e. centrifugal pumps). | * The 2042 model sized for "normal duty" (ND) 15 HP which is appropriate for variable torque (VT) applications (i.e. centrifugal pumps). | ||
* Internal PCBs are conformally coated (IEC 60721-3-3, Class 3C2 for chemical gasses). <b>This is a huge plus!</b> | * Internal PCBs are conformally coated (IEC 60721-3-3, Class 3C2 for chemical gasses). <b>This is a huge plus!</b> | ||
| Line 125: | Line 111: | ||
* 391 W total loss @ 2 kHz, 42 A output. | * 391 W total loss @ 2 kHz, 42 A output. | ||
== | {| class="wikitable" | ||
!colspan="2"|Drive Catalog Code | |||
!Description | |||
!Comment | |||
|- | |||
!Product Series | |||
|GA50 | |||
| | |||
| | |||
|- | |||
!Region Code | |||
|U | |||
|Americas | |||
| | |||
|- | |||
!Input Power Supply Voltage | |||
|2 | |||
|Three-Phase AC 200 V Class | |||
| | |||
|- | |||
!Rated Output Current | |||
|42 | |||
|42 A | |||
| | |||
|- | |||
!EMC Noise Filter | |||
|A | |||
|No Internal EMC Filter | |||
| | |||
|- | |||
!Enclosure Protection Design | |||
|B | |||
|IP20/UL Open Type | |||
| | |||
|- | |||
!Environmental Specification | |||
|A | |||
|Standard | |||
| | |||
|} | |||
==== Prior Considerations ==== | |||
VFDs from various manufacturers were considered during the evaluation process. In particular, the following other drives were evaluated: | |||
* ABB ACS310-03U-50A8-2+J400 | |||
* Automation Direct GS23-2015 | |||
* Automation Direct GS4-2015 | |||
=== Line Reactor === | === Line Reactor === | ||