Line 425: Line 425:


NOTE: The flow meter was previously a GF Signet MK515.3P1.  Erratic behavior prompted its replacement in early June 2021.
NOTE: The flow meter was previously a GF Signet MK515.3P1.  Erratic behavior prompted its replacement in early June 2021.
=== Power Budget ===
{| class="wikitable"
!Item
!Consumption
!Comments
|-
|Lantronix PremierWave XN
|94 mA
|Per the spec sheet, the device consumes 2.25 W @ 30 VDC.  Using the same figure for 24 VDC.
|-
|Pressure Tank Sensors (4)
|80 mA
|A quantity of 4 x 4-20 mA sensors.
|-
|Depth Sensor
|20 mA
|A single 4-20 mA sensor.
|-
|Flow Meter
|20 mA
|A single 4-20 mA sensor.
|-
|Digital Inputs (10)
|85 mA
|On the PLC base, X0 to X3 consume 13 mA, X4 to X23 consume 8.5 mA.  Assuming ten digital inputs.
|-
|Relays (3)
|112.5 mA
|Each coil has a nominal resistance of 640 Ohms (37.5 mA @ 24 VDC).
|-
|Stack Light
|50 mA
|The LME-302L consumes 18 mA per red/yellow and 14 mA for green.
|-
|Programmed Stop Button
|26 mA
|
|-
|Total
|487.5 mA
|
|}


=== Drawings ===
=== Drawings ===