Pool Boiler: Difference between revisions

Jump to navigation Jump to search
no edit summary
No edit summary
Line 33: Line 33:


=== Stage C ===
=== Stage C ===
== Control Interlocks ==
The list below includes interlocks with electrical interfaces only and is intended to align with the CSD-1.  This table is for reference only; the CSD-1 should always be considered the master.
{| class="wikitable"
!Control/Device
!ANSI CSD-1<br>Reference(s)
!Manufacturer
!Model
!Setpoint<br>(align with CSD-1)
|-
|Low-Water [Fuel] Cutout
|CW-110<br>CW-120<br>CW-150
|ITT
|PS-851-M-120
|N/A (not adjustable)
|-
|Forced Circulation
|CW-200<br>CW-210(b)
|ITT
|FS-251
|N/A (not adjustable)
|-
|Water Temperature
|CW-410(b)
|Red Lion
|T4820219
|82 &deg;F
|-
|High Water Temp Limit
|CW-210(b)
|Johnson Controls
|CC450CCN-3
|180 &deg;F
|-
|Combustion Air Switch
|CF-220
|Cleveland Controls
|AFS-1
|0.5" WC
|-
|Purge Air Flow (Pre-Ignition)
|CF-210
|UTEC
|1003-638A
|30 seconds
|-
|Flame Safeguard (Primary)
|CF-310<br>CF-320
|UTEC
|1003-638A
|N/A (not adjustable)
|-
|Flame Detector<br>(via RBI 3316-0327)
|CF-310<br>CF-320
|UTEC
|1003-638A
|12 &micro;A
|}