Pool Boiler: Difference between revisions
Jump to navigation
Jump to search
no edit summary
Matt Parnell (talk | contribs) |
Matt Parnell (talk | contribs) No edit summary |
||
| Line 33: | Line 33: | ||
=== Stage C === | === Stage C === | ||
== Control Interlocks == | |||
The list below includes interlocks with electrical interfaces only and is intended to align with the CSD-1. This table is for reference only; the CSD-1 should always be considered the master. | |||
{| class="wikitable" | |||
!Control/Device | |||
!ANSI CSD-1<br>Reference(s) | |||
!Manufacturer | |||
!Model | |||
!Setpoint<br>(align with CSD-1) | |||
|- | |||
|Low-Water [Fuel] Cutout | |||
|CW-110<br>CW-120<br>CW-150 | |||
|ITT | |||
|PS-851-M-120 | |||
|N/A (not adjustable) | |||
|- | |||
|Forced Circulation | |||
|CW-200<br>CW-210(b) | |||
|ITT | |||
|FS-251 | |||
|N/A (not adjustable) | |||
|- | |||
|Water Temperature | |||
|CW-410(b) | |||
|Red Lion | |||
|T4820219 | |||
|82 °F | |||
|- | |||
|High Water Temp Limit | |||
|CW-210(b) | |||
|Johnson Controls | |||
|CC450CCN-3 | |||
|180 °F | |||
|- | |||
|Combustion Air Switch | |||
|CF-220 | |||
|Cleveland Controls | |||
|AFS-1 | |||
|0.5" WC | |||
|- | |||
|Purge Air Flow (Pre-Ignition) | |||
|CF-210 | |||
|UTEC | |||
|1003-638A | |||
|30 seconds | |||
|- | |||
|Flame Safeguard (Primary) | |||
|CF-310<br>CF-320 | |||
|UTEC | |||
|1003-638A | |||
|N/A (not adjustable) | |||
|- | |||
|Flame Detector<br>(via RBI 3316-0327) | |||
|CF-310<br>CF-320 | |||
|UTEC | |||
|1003-638A | |||
|12 µA | |||
|} | |||
== Maintenance == | == Maintenance == | ||