Pool Systems Automation: Difference between revisions
Jump to navigation
Jump to search
→Operation
Matt Parnell (talk | contribs) |
Matt Parnell (talk | contribs) |
||
| Line 27: | Line 27: | ||
The main pump motor determines the operating state. | The main pump motor determines the operating state. | ||
{| class="wikitable" | |||
!State | |||
!LCD Notification | |||
!Condition(s) | |||
!Stack Light | |||
|- | |||
|Pump Stopped | |||
|<tt>Pump Stopped</tt> | |||
|The default state upon initialization. Set when the pump is stopped. | |||
|Red (Flashing) | |||
|- | |||
|Pump Startup | |||
|<tt>Pump Startup</tt> | |||
|The pump is starting up (a 10-second static delay once the motor starter contacts are closed). | |||
|Off | |||
|- | |||
|Operating | |||
|<tt>Pump Operating</tt> | |||
| | |||
|Green/Yellow (Flashing) | |||
|- | |||
|Backwash | |||
|<tt> | |||
| | |||
|Alternating Red-Green | |||
|} | |||
==== Filter Tank Pressure ==== | ==== Filter Tank Pressure ==== | ||
| Line 41: | Line 68: | ||
!Stack Light | !Stack Light | ||
|- | |- | ||
| | |Operating | ||
|< 8 psi | |< 8 psi | ||
|Pressure Low | |Pressure Low | ||
| Line 47: | Line 74: | ||
|Yellow | |Yellow | ||
|- | |- | ||
| | |Operating | ||
|≥ 8 psi and < 18 psi | |≥ 8 psi and < 18 psi | ||
|Pressure OK | |Pressure OK | ||
| Line 53: | Line 80: | ||
|Green (unless overridden) | |Green (unless overridden) | ||
|- | |- | ||
| | |Operating | ||
|≥ 18 psi | |≥ 18 psi | ||
|Pressure High | |Pressure High | ||
| Line 60: | Line 87: | ||
|} | |} | ||
When in the <b>Pump Startup</b>, <b> | When in the <b>Pump Startup</b>, <b>Operating</b> or <b>Backwash</b> state, each tank pressure is briefly shown on the LCD in psi. If the value is not valid, <tt>Fault</tt> is shown in place of a pressure value. | ||
==== Water Flow ==== | ==== Water Flow ==== | ||