=== Wiring === | === Wiring === | ||
Shielded VFD cabling may be required to contain high-frequency emissions. Automation Direct has #8 AWG 4-conductor XLPE insulated shielded cable, rated for 50 A at 75 °C (NEC 310.15 (B), assumes 30 °C ambient) for $8.08/ft. The cable is made in USA by Southwire. This cable has an OD of 0.87 inches and minimum bend radius of 10 inches. Calculations suggest a 1-1/4" conduit may be necessary to pull a cable of this diameter with adequate fill margin. The existing PVC conduit appears to be about 3/4" (to confirm), which would need to be replaced. | Shielded VFD cabling may be required to contain high-frequency emissions. Automation Direct has #8 AWG 4-conductor XLPE insulated shielded cable, rated for 50 A at 75 °C (NEC 310.15 (B), assumes 30 °C ambient) for $8.08/ft (August 2021 pricing). The cable is made in USA by Southwire. This cable has an OD of 0.87 inches and minimum bend radius of 10 inches. Calculations suggest a 1-1/4" conduit may be necessary to pull a cable of this diameter with adequate fill margin. The existing PVC conduit appears to be about 3/4" (to confirm), which would need to be replaced. | ||
A load reactor likely will not be used, nor does it necessarily eliminate the need for shielded VFD cabling. | A load reactor likely will not be used, nor does it necessarily eliminate the need for shielded VFD cabling. | ||