==== Water Flow ====
==== Water Flow ====
Output water flow is monitored by a paddle wheel flow meter that generates a sine wave with a frequency proportional to the flow rate.  A flow "transmitter" (GF Signet 8512) translates that analog output from the flow meter into a 4-20 mA signal proportional to the flow rate.
A value is considered valid if the current measured is greater than or equal to 4 mA (not an open circuit).  The low and high thresholds are based upon the required flow turnover rate for the pool volume.
{| class="wikitable"
!Qualifier
!Threshold
!Result
!LCD Notification
!Stack Light
|-
|Operating
|< 570 GPM
|Low Flow Rate
|<tt>Out Flow L</tt>
|Yellow
|-
|Operating
|&GreaterEqual; 570 GPM and < 670 GPM
|Flow Rate OK
|None
|Green (unless overridden)
|-
|Operating
|&GreaterEqual; 670 GPM
Flow Rate High
|<tt>Out Flow H</tt>
|Yellow
|}
When in the <b>Pump Startup</b> or <b>Operating</b> state, the flow rate is briefly shown on the LCD in GPM.  If the value is not valid, <tt>Fault</tt> is shown in place of a flow rate value.