Pool Main Pump Motor: Difference between revisions

Jump to navigation Jump to search
no edit summary
No edit summary
Line 8: Line 8:


In the future, a VFD may be used to reduce the motor speed, eliminating the need for manual adjustment via a valve.
In the future, a VFD may be used to reduce the motor speed, eliminating the need for manual adjustment via a valve.
== Measurement Data ==
=== September 2021 ===
==== Voltage ====
{| class="wikitable"
!L1 to GND
|117 VAC
|-
!L2 to GND
|211 VAC
|-
!L3 to GND
|120 VAC
|}
{| class="wikitable"
!L1 to L2
|240 VAC
|-
!L2 to L3
|240 VAC
|-
!L3 to L1
|238 VAC
|}
==== Current ====
{| class="wikitable"
!
!Trial #1
!Trial #2
!Trial #3
!Trial #4
|-
!L1
|34.3 A
|35.2 A
|27.8 A
|32.5 A
|-
!L2
|35.5 A
|36.0 A
|29.2 A
|33.6 A
|-
!L3
|32.2 A
|33.2 A
|26.2 A
|30.4 A
|-
!Tank Pressures
|9-10 psi
|11-12 psi
|0-1 psi
|5-6 psi
|-
!Flow Rate
|617 GPM
|694 GPM
|248 GPM
|476 GPM
|}
* <b>Trial #1:</b> The out flow valve is cut back to just shy of 45&deg;.
* <b>Trial #2:</b> The out flow valve is fully open.
* <b>Trial #3:</b> The out flow valve is cut back far (very restricted).
* <b>Trial #4:</b> The in flow valve is very restricted.