Pool Systems Automation: Difference between revisions
→Serial Interfaces
Matt Parnell (talk | contribs) |
Matt Parnell (talk | contribs) |
||
| Line 344: | Line 344: | ||
==== Serial Interfaces ==== | ==== Serial Interfaces ==== | ||
The DL06 PLC has two serial interfaces. Each port is connected to a port on the Lantronix Premierwave XN. The configuration as follows: | The DL06 PLC has two built-in serial interfaces. Each port is connected to a port on the Lantronix Premierwave XN. The configuration as follows: | ||
{| class="wikitable" | {| class="wikitable" | ||
| Line 356: | Line 356: | ||
|RS-232 | |RS-232 | ||
|9600 8O1/None | |9600 8O1/None | ||
|Programming | |Local Programming<br>(using interface cable) | ||
|Port 2 | |Port 2 | ||
|- | |- | ||
| Line 362: | Line 362: | ||
|RS-232 | |RS-232 | ||
|38400 8N1/None | |38400 8N1/None | ||
|Modbus Slave ([[Pool Systems Dashboard|dashboard monitoring]]) | |Modbus Slave<br>([[Pool Systems Dashboard|dashboard monitoring]]) | ||
|Port 1 | |Port 1 | ||
|- | |||
|<b>Planned:</b> D0-DCM Port 1 | |||
|RS-232 | |||
|Default | |||
|Not Used<br>(spare) | |||
|N/A | |||
|- | |||
|<b>Planned:</b> D0-DCM Port 2 | |||
|RS-485 | |||
|19200 8N1 | |||
|Modbus Master<br>([[Pool Main Pump Motor|VFD]] and [[Boiler Temperature Controller|boiler temperature control]]) | |||
|N/A | |||
|} | |} | ||
Notes: | |||
* Port 1 is limited to 9600 baud, odd parity and RS-232 communication. | |||
=== Sensors === | === Sensors === | ||