==== Fuji Electric FRN0047C2S-2U ==== | |||
* 47.0 FLA (21 % margin for 37 FLA) | |||
* 10.24" H x 8.66" W x 7.48" D | |||
* No STO | |||
==== Hitachi WJ200-110LF ==== | |||
* 56.0 FLA VT (34 % margin for 37 FLA) | |||
* 11.65" H x 7.09" W x 6.89" D | |||
* With STO | |||
* DC Reactor: DCL-L-11 | |||
* Input Side AC Reactor: ALI-22L2 | |||
* Input Side Noise Filter: NF-L60 | |||
* Radio Noise Filter: ZCL-A (Zero-Phase Reactor) or CFI-L (Capacitor Filter) | |||
==== DURApulse GS20 Series GS23-2015 ===== | |||
* 51 FLA VT (27 % margin for 37 FLA) | |||
* Frame Size "E": 9.84" H x 5.12" W x 7.28" D | |||
* With STO (TUV Certified) | |||
* Conduit Box: GS20A-N1E ($29) | |||
* EMC Filter & Zero-Phase Reactor: RF008X00A | |||
* Input Fuse: 110 A, TJN110 (Fast-Acting Class T) or JHL110 (Edison Class J) | |||
* Line/Load Reactor: LR-2020 ($181.00) | |||
* AC Output Filter (VTF): VTF-246-NRS | |||
=== Wiring === | === Wiring === | ||