Pool Boiler: Difference between revisions

Line 15: Line 15:
A demand for heat is satisfied when all of the following conditions are met:
A demand for heat is satisfied when all of the following conditions are met:


# The boiler temperature controller [[Pool Boiler Temperature Controller#Low Operator|low operator]] relay contact is closed, indicating that no faults are active.
# The measured temperature (via the [[Pool Temperature Controller|pool temperature controller]]) has reached or fallen below the heat threshold.
# The measured temperature (via the [[Pool Temperature Controller|pool temperature controller]]) has reached or fallen below the heat threshold.
# The normally closed (NC) <b>Boiler Disable</b> relay contact (part of the pool automation system) is closed, indicating that no fault is observed.
# The normally closed (NC) <b>Boiler Disable</b> relay contact (part of the pool automation system) is closed, indicating that no fault is observed.
# The boiler temperature controller [[Pool Boiler Temperature Controller#Low Operator|low operator]] relay contact is closed, indicating that no faults are active.
 
NOTE: These three conditions align with the low operator temperature switch from #11 to #13, "remote operator option" function from #13 to #14 and "enable relay option" from #14 to #15 in RBI drawing 42-2112.  Connections at terminals #13 and #14 are no longer made within the boiler housing.


At this point:
At this point: