Pool Boiler: Difference between revisions

Jump to navigation Jump to search
Line 13: Line 13:
=== Stage A: Demand for Heat ===
=== Stage A: Demand for Heat ===


A demand for heat is satisfied when all of the following conditions are met:
A demand for heat occurs when all of the following conditions are met:


# The boiler temperature controller [[Pool Boiler Temperature Controller#Low Operator|low operator]] relay contact is closed, indicating that no faults are active.
# The boiler temperature controller [[Pool Boiler Temperature Controller#Low Operator|low operator]] relay contact is closed, indicating that no faults are active.
# The measured temperature (via the [[Pool Temperature Controller|pool temperature controller]]) has reached or fallen below the heat threshold.
# The measured temperature (via the [[Pool Temperature Controller|pool temperature controller]]) has dropped to the heat threshold, which closes the relay contact.
# The normally closed (NC) <b>Boiler Disable</b> relay contact (part of the pool automation system) is closed, indicating that no fault is observed.
# The normally-closed <b>Boiler Disable</b> relay contact (part of the pool automation system) is closed (relay not activated), permitting boiler operation (no fault observed).


NOTE: These three conditions align with the low operator temperature switch from #11 to #13, "remote operator option" function from #13 to #14 and "enable relay option" from #14 to #15 in RBI drawing 42-2112.  Connections at terminals #13 and #14 are no longer made within the boiler housing.
NOTE: These three interlocks align with the LOW OPERATOR temperature switch from #11 to #13, REMOTE OPERATOR OPTION function from #13 to #14 and ENABLE RELAY OPTION from #14 to #15 in RBI drawing 42-2112.  Connections at terminals #13 and #14 are no longer made within the boiler housing.


At this point:
If all three interlocks are satisfied:


# The boiler time-delay relay TD4 (blower delay post-purge) is engaged, which immediately energizes contactor C1, turning on the boiler loop circulation pump.
# The automation system relay CR2110 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X10]].
# The automation system relay CR2110 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X10]].


=== Stage B: Flow/Temperature Interlocks ===
=== Stage B: Temperature and Water Flow OK ===


The following interlocks must be satisfied to proceed:
The temperature and water flow are deemed OK when:


# The <b>High Temp</b> latch is not set (in the Honeywell L4006E, with a reset pushbutton located on the front side of the boiler).
# The <b>High Temp</b> latching switch is not closed (in the Honeywell L4006E, with a reset pushbutton located on the front side of the boiler).  This is a normally-closed switch; the switch is closed when the high-temperature latch is not set.
# The <b>Water Flow</b> switch is tripped, indicating that sufficient flow in the loop is present.
# The <b>Water Flow</b> switch is closed, indicating that sufficient flow in the loop is present.


At this point:
NOTE: These two interlocks align with the HIGH TEMP temperature switch from #15 to #17 and WATER FLOW switch from #18 to #21.  JUMPER F is in place; the low-water cut-off interlock is located earlier in the chain.
 
If the <b>High Temp</b> interlock is satisfied:
 
# The boiler time-delay relay TD4 (blower delay post-purge) is engaged, which immediately energizes contactor C1, turning on the boiler loop circulation pump.  Activation of the pump should result in closure of the <b>Water Flow</b> switch.
 
If both the <b>High Temp</b> and <b>Water Flow</b> interlocks are satisfied:


# The boiler time-delay relay TD3 (pump delay post-purge) is engaged, which immediately energizes contactor C2, turning on the blower motors (low speed).
# The boiler time-delay relay TD3 (pump delay post-purge) is engaged, which immediately energizes contactor C2, turning on the blower motors (low speed).
# The automation system relay CR2111 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X11]].
# The automation system relay CR2111 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X11]].


=== Stage C ===
=== Stage C: Low Air Pressure OK ===
 
The low air pressure switch closes in response to sufficient positive pressure in the combustion chamber.
 
Once the <b>Low Air Pressure</b> interlock is satisfied:
 
# The boiler time-delay relay TD1 (blower delay pre-purge) is engaged.
 
Once the TD1 delay has elapsed:
 
# The flame sense module (FSM) is powered, which opens the pilot gas valve.  Relay R7 is engaged, which powers the spark generator transformer.
# The automation system relay CR2112 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X12]].


Description pending.
NOTE: Flame fail/lockout is not considered here.


=== Stage D ===
=== Stage D ===

Navigation menu