Pool Boiler: Difference between revisions

Jump to navigation Jump to search
Line 56: Line 56:
# The automation system relay CR2112 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X12]].
# The automation system relay CR2112 is energized, which activates [[Pool Systems Automation#Digital Inputs|PLC input X12]].


NOTE: Flame fail/lockout is not considered here.
NOTE: Flame fail/lockout is not considered here.  The present flame sense module (FSM), or "intermittent pilot ignition" module, does not include alarm contacts.  The alarm contacts are required to engage R1, the flame fail/lockout relay.  This is problematic, as it would allow the ignition transformer to spark indefinitely, eventually resulting in component failure.  As a work-around, the automation system provides a monitored lockout function via the <b>Boiler Disable</b> relay.


=== Stage D ===
=== Stage D ===