Pool Main Pump Motor
The main pool pump motor at the facility (as of August 2021) is a Leeson Model C254T17DK13A (catalog #199987.00). It is rated for 15 HP (11 kW), 37 FLA @ 230 VAC. It is inverter duty rated (confirmed by the local manufacturer's rep) with a 10:1 PWM ratio (60 Hz, 1770 RPM down to 6 Hz, 177 RPM).
It has a month/year manufacturing designation of "H2016" - presumably corresponding with August (H=8) 2016. This makes sense, as the pump was noted to have been replaced in early 2017.
Wiring and Fuse Protection
The existing motor is fed by 3 x TBD (#10 AWG GND). Fused with 3 x FRN-R-60 (60 A) fuses.
Power Factor Correction Capacitor (PFCC)
At present (as of August 2021), no power factor correction capacitor (PFCC) is in use. It was decided that given cost priorities, a PFCC would not offer sufficient payback to justify its purchase.
Myron Zucker was contacted in August 2020 and provided two options, both rated for 240 VAC, 5 kVAr, 3-phase, 60 Hz:
- KNM23005-3 (NEMA 12 for indoor use, 14" H x 9.25" W x 5.25" D)
- KNM23005-3N3 (NEMA 3R suitable for outdoor use, 16" H x 12" W x 6" D)
Applying a 5 kVAr PFCC would reduce the FLA from 37 A to 31 A. This would reduce i-squared-R losses by 6 A. Actual losses are then based upon the cable run.
Variable Frequency Drive (VFD)
IMPORTANT: At this time, this section is for investigation purposes only. It has not been determined when/if a VFD will be implemented.
High-Leg Delta
A major issue/question remains to be answered: Can any VFD reliably operate with high-leg delta service as is present at the club?
Configuration
- Variable Torque (VT) for pump control (power is proportional to the cube of the speed)
Safety
Options
All drives are sized to drive a 15 HP motor, 230 VAC three-phase.
Unless otherwise noted, all support Modbus RTU (via RS-485).
- Fuji Electric FRN0047C2S-2U
- 47.0 FLA
- 10.24" H x 8.66" W x 7.48" D
- No STO
- Hitachi WJ200-110LF
- 56.0 FLA VT
- 11.65" H x 7.09" W x 6.89" D
- With STO
- DC Reactor: DCL-L-11
- Input Side AC Reactor: ALI-22L2
- Input Side Noise Filter: NF-L60
- Radio Noise Filter: ZCL-A (Zero-Phase Reactor) or CFI-L (Capacitor Filter)
- DURApulse (Automation Direct) GS23-2015 ($567.50)
- 51 FLA VT
- Frame Size "E": 9.84" H x 5.12" W x 7.28" D
- Clearance
- With STO (TUV Certified)
- Conduit Box: GS20A-N1E ($29)
- EMC Filter & Zero-Phase Reactor: RF008X00A
- Input Fuse: 110 A, TJN110 (Fast-Acting Class T) or JHL110 (Edison Class J)
- Line/Load Reactor: LR-2020 ($181.00)
- AC Output Filter (VTF): VTF-246-NRS
Wiring
- #4 AWG? (75 °C rated)